D. frame the fireplace, C. sidewalls/surrounds, 4 in. [102 mm – Hearth and Home Technologies I60 User Manual

Page 20

Advertising
background image

20

B

C

A

2 in. (51 mm)
min. air space
clearance
from chimney.

Note: Framing must be
extended straight up,
all the way to the ceiling.

Header MUST NOT be notched!

D

D = extra space needed for outside air connection.
If outside air duct has no bend, this dimension may be
reduced as long as minimum clearances are met.

B

A

24 in.

[610 mm]

19 3/4 in.

[502 mm]

24 in.

[610 mm]

28 5/8 in.

[727 mm]

FLUSH
FRONT

4 in.

[102 mm]

BRICK

FRONT

50° angle

39°

angle

Note: Grid depicts 1-in scale.

D. Frame the Fireplace

Figure 6.4 shows typical framing using combustible materials (2x4 lumber shown).

• Observe all required air space clearances to combustible materials as shown in Figure 6.1 & 6.2.
• Framing across the top of fi replace must be above top standoffs.

Figure 6.4 Framing the Fireplace

C. Sidewalls/Surrounds

• Adjacent combustible sidewalls must be located a minimum 24 in. (610 mm) from the fi replace opening.
• Combustible and noncombustible mantel legs, surrounds and stub walls may be constructed within the gridded area,

Figure 6.3.

Figure 6.3 Mantel Leg or Wall Projections (Acceptable on both sides of opening)

Model

A

B

I60

inches

36

45

mm

914

1130

I80

inches

42

50 1/2

mm

1067

1283

Model

A

B*

C**

D

(4” duct)

D

(6” duct)

I60

in.

45 1/2

28

50

8

12

mm

1156

711

1270

203

305

I80

in.

51 1/2

28 1/2

50

8

12

mm

1308

724

1270

203

305

* If interior of chase will be drywalled, add the thickness to
this measurement.

** Adjust header height for a raised fl oor under fi replace.

Heatilator • I60, I80 • 4013-250 • Rev C • 11/08