G. place protective metal hearth strips, H. level fireplace – Hearth and Home Technologies I60 User Manual

Page 24

Advertising
background image

24

)))

)))))))))))))))))

))))

)))))))

)))

))

))))))

))

)))

))

))))))))

))))

))

))

))

))

))

))))

)))))))

)))

)))

)))

))))))

3 ft min. from
top of uppermost
chimney section
to air inlet.

Protective metal strips are placed 2 in. (51 mm) under the
front of the fireplace and must extend beyond the front
and sides of fireplace opening by 2 in. (51 mm).

1 in. (25 mm)
overlap

Figure 7.14 Position the Protective Metal Hearth Strips

G. Place Protective Metal Hearth Strips

WARNING! Risk of Fire! Protective metal hearth strips
MUST be installed. DO NOT cover metal strips with com-
bustible materials. Sparks or embers may ignite fl ooring.

• Refer to Figures 7.14 and 7.15.
• Locate the two protective metal hearth strips measuring

approximately 26 in. x 4 in. (660 mm x 102 mm) included
with this fi replace.

• Slide each metal strip 2 in. (51 mm) under front edge of

fi replace.

• Overlap strips in the middle of fi replace opening by 1 in.

(25 mm) minimum..

• Metal strips must extend beyond the front and sides of

the fi replace opening by at least 2 in. (51 mm).

• Protect the front of a platform elevated above the hearth

extension with metal strips (not included with fi replace)
per Figure 7.16. See Section 11 for hearth extension
instructions.

H. Level Fireplace

• Level

fi replace side-to-side and front-to-back.

• Shim with non-combustible material as necessary.
• Secure

fi replace to framing with nailing fl anges with a

minimum of two fasteners per nailing fl ange.

• Check

fi replace opening for square to ensure proper fi t

of glass doors. Measure diagonals of fi replace opening
to make sure they are equal.

Raised Platform

Floor

2 in.

(51 mm)

1 in. (25 mm) min.

overlap

2 in.

(51 mm)

Top piece must overlap

bottom piece

Figure 7.15 Protect the Front of an Elevated Platform

Heatilator • I60, I80 • 4013-250 • Rev C • 11/08

Figure 7.16 Possible Outside Air Inlet Locations

Note: Chimney air kit and
11-10 in./279 -25 4 mm
adapter are not shown, but
are required in Canada.