I. install outside air kit – Hearth and Home Technologies I60 User Manual

Page 25

Advertising
background image

25

Outlet placed

higher than 3 ft

below the

termination cap

Attic space

Garage or

combustible

liquids storage

Outlet blocked by

snow, leaves, etc.

Clear area

outside

house or in

ventilated

crawl space

YES

NO

NO

NO

NO

Use only duct materials specified
by manufacturer (preferably with
short run or mainly straight duct,
except small dip for cold air trap
which will help prevent flow of cold air).

Factory-built

fireplace

Figure 7.17 Outside Combustion Air Placement

Outside Air

Hood

Outside Air

Plate

Assembly

2 Wire Ties

Flexible Duct

(not supplied)

Figure 7.18 Outside Air Installation

I. Install Outside Air Kit

CAUTION! Risk of Fire or Asphyxiation! DO NOT draw

outside combustion air from wall, fl oor or ceiling cavity,
or enclosed spaces such as an attic or garage.

DO NOT place outside air hood close to exhaust
vents or chimneys. Fumes or odor could be drawn
into the room through the fi replace.

• Locate outside air inlet to prevent blockage from

leaves, snow/ice, or other debris. Blockages could
cause combustion air starvation.

• Keep duct runs short and straight to minimize restriction.

A small dip is acceptable for a cold air trap.

• The outside air kit must be installed on the left hand side

of the fi replace.

• Locate the outside air hood in a clear area, preferably

into prevailing wind during the heating season. Refer to
Figure 5.2.

• Install as shown in Figures 7.16, 7.17 and 7.18.
• The air duct may be run vertically.
• The outside air hood must be at least 3 ft (.91 m) below

the top of the uppermost chimney section.

Heatilator • I60, I80 • 4013-250 • Rev C • 11/08

Advertising
This manual is related to the following products:

I80