A. Chimney Requirements

Measure vertical distances from the base of the fi replace
as shown in Figure 8.2.

6 ft (1.8 m) max.
unsupported run

20 ft (6 m) max.
pipe between an
offset & return

Ceiling Firestop

35 ft (10.7 m)

max. straight

unsupported

chimney height

18.5 ft (5.6 m) min. height

single offset-return

24 ft. (7.3 m) min. height

double offset-return

90 ft (27.4 m) max. height

6 ft (1.8 m) max.
unsupported chimney
above roof

55-1/2 in.

(1410 mm)

Effective Height

(bottom of fireplace

to top of starter collar)

11-10 in./279-254mm

adaptor required in

Canada

Figure 8.2 Chimney Requirements

Table 8.1

ft

m

Minimum overall straight height

18

5.49

Minimum height with offset/return

18.5

5.64

Maximum height

90

27.43

Maximum chimney length between an
offset and return

20

6.10

Maximum distance between chimney
stabilizers`

35

10.67

Double offset/return minimum height

24

7.32

Maximum unsupported chimney length
between the offset and return

6

1.83

Maximum unsupported chimney height
above the fi replace

35

10.67

Maximum unsupported chimney above
roof

6

1.83

WARNING! Risk of Fire! You must maintain 2 in. (51
mm) air space clearance to insulation and other combus-
tible materials around the chimney system. Failure to do
so may cause overheating and fi re.

Determine the chimney components needed to complete
your particular installation:

• Measure the total vertical height of the fireplace

installation from the base of the fi replace assembly to
the approximate location of the bottom of the termination
cap.

• Subtract the effective height of the fi replace assembly

(see Figure 8.2) from the total vertical height to determine
the overall height of the chimney installation.

• Create a schematic for your application similar to Figure

8.2 showing components required (referring to Table
8.1). Figure 8.1 identifi es those components and where
used.

• Install a ceiling fi restop whenever the chimney penetrates

a fl oor/ceiling.

NOTICE:

A maximum of two pairs of offsets and returns

may be used.

CAUTION! Risk of Fire and/or Asphyxiation! DO

NOT connect this fi replace to a chimney fl ue servicing
another appliance. DO NOT connect to any air distribu-
tion duct or system. These actions could cause over-
heating/fi re in the chimney fl ue, or release of exhaust
fumes into the living areas.

Heatilator • I60, I80 • 4013-250 • Rev C • 11/08

HEIGHT OF CHIMNEY COMPONENTS

in.

mm

US

Canada ONLY

Chimney Stabilizer

SL11

SL4

4-3/4

121

Ceiling Firestops

FS538

FS538

0

0

FS540

FS540

0

0

Offsets/Returns

SL1130

SL430

14-1/2

368

Roof Flashing

RF570

RF570

0

0

RF571

RF571

0

0

Chimney Sections*

SL1106

SL406

4-3/4

121

SL1112

SL412

10-3/4

273

SL1118

SL418

16-3/4

425

SL1136

SL436

34-3/4

883

SL1148

SL448

46-3/4

1187

n/a

SLA10

16-3/4

425

* Dimensions refl ect effective height.

О

Advertising
This manual is related to the following products:

I80