Venting installation – FMI MASONRY FIREBOX MM33 User Manual

Page 12

Advertising
background image

www.fmiproducts.com

125160-01A

12

CaUTIon: Combustion air inlet ducts shall

not terminate in attic space.

The maximum height for the air vent can not

exceed 3 feet below the flue gas outlet of the

termination.

FaCToRY BUIlT CHIMneY sYsTeMs

The Grand Meridian is designed to be installed with

1)

FMI PRODUCTS, LLC Metal Chimney System.
This Grand Meridian fireplace is intended as a

2)

supplemental heat source only. It is not intended

as a primary heat source.
It is the responsibility of the contractor/installer

3)

(not the manufacturer) to ensure that adequate

combustion air is provided for proper function of

this fireplace. Fireplaces take up a large volume of

replacement air from outside the house and if the

house is of airtight construction, smoke spillage

may occur if proper draft is not achieved.
There are many conditions beyond the

4)

manufacturer’s control regarding improper fireplace

operation. The manufacturer cannot ensure

“smoke free” operation, nor can the manufacturer

take on the responsibility for problems with

surrounding construction; chimneys that have not

venting installation

Figure 13 - Outside Air Kit Venting

Secure to Collars with Metal Tape, Screws

or Straps (Min. of 1/4" x 20" in size)

Air Inlet

Location

Must

Allow For

Bushes

or Snow

Vent Hood

Required

for Wall

Installation

Vented Crawl

Space (Check

Local Codes

Before Installing

in a Vented

Crawl Space)

oPTIonal oUTsIde aIR KIT (Model MM4aK)

The Grand Meridian Fireplace needs enough re-

placement air to function properly and some local

building codes may require outside combustion air

to be provided. If no replacement air is provided,

improper flue drafting may occur, creating negative

pressure whereby smoke may enter the home, es-

pecially in homes that are very well insulated and

tightly sealed. Check local building codes for specific

requirements.
The installation of an outside air kit should be per-

formed during the rough framing of the fireplace due

to the nature of it's location. Outside combustion air

is accessed through a vented crawl space or through

a sidewall (Figure 13). If crawl space is used, check

local codes for proper termination.

Be sure that you carefully check the source of the

outside air before you choose the site for your air in-

take. You don’t want a place where snow will collect,

where bushes or trees will be growing or a location

that is too close to any other structure.
Install Combustion Air Kit into the firebox through the

side wall opening provided. A 4" dia. hole will also be

required through the firebrick side lining (see Figure

12). The tubing that goes out of the firebox wall must

feed into a flexible metal conduit as the source for

outside combustible air. Install a screened termina-

tion cap to keep out small animals.

Figure 12 - Outside Air Kit Installation

Advertising
This manual is related to the following products: