Supporting floor system installation – FMI MASONRY FIREBOX MM33 User Manual

Page 18

Advertising
background image

www.fmiproducts.com

125160-01A

18

supporting Floor system installation

It is the ultimate responsibility of the installer to en-

sure that proper concrete slab supports are used.

WaRnInG to the licensed design professional

and/or building contractor: It is your responsibility

to be certain that the Grand Meridian can be

properly supported by the combustible floor

system on which the fireplace will rest.

For fireplace support foundations installed on con-

crete refer to Appendix I and II (

pages 42 & 43

) for

specific instructions.

ReBaR loCaTIons

Lay-out the position of the fireplace and drill holes

where the rebar will be located. Secure the #3 rebar

4 inches into the concrete foundation with ITW Epoxy

or Simpson Epoxy. Follow manufacturer’s instruc-

tions for installation of rebar into slab.

Wood FlooR

Anchorage of fireplace to wood floor construction is

required. Refer to Figure 29 on page 20 for anchor-

age dimensions. Four anchors are required to attach

to the sub-flooring framing.

CRaWl sPaCe oR UPPeR FlooR:

For installation of firebox over combustible crawl

spaces or upper floors, anchorage of the firebox is

required. Illustrations of examples of possible an-

chorage methods are shown in Figures 26 thru 28

depending upon the type of floor framing. Final meth-

od of anchorage is to be determined by licensed de-

sign professional.
For conventional framing, where the floor joists are

parallel with the sides of the firebox, the addition of

floor joists to align with the anchor brackets allows the

brackets to be directly connected to the floor joists.
NOTE: Additional floor joists may be required to sup-

port the weight of the firebox and chimney. Where

the floor joists run parallel to the front of the firebox,

anchorage can be accomplished in like manner as

shown in Figure 26 using blocking between the floor

joist.

For floors supported by I-Joists, the method of an-

chorage is illustrated in Figures 27 and 28, page 19.

Figure 31, page 20 illustrates the general arrange-

ment of anchorage to floor framing.
It is important to take into consideration that the load

for the Grand Meridian Fireplace must be considered

as additional dead load that will have to be supported

by the floor framing. Additional floor joists or I-joists

may be required as determined by the licensed de-

sign professional.
The dead weights for the fireplace are noted in Table

I. It is the task and responsibility of the general con-

tractor/installer to see that the proper reinforcement

for weight loads are made by a licensed design pro-

fessional prior to the fireplace installation.
As stated above, it is desirable to place additional

framing for alignment of anchor rods. Refer to Figure

29, page 20 for anchor rod locations.
Attach the firebox side wall anchors to steel sup-

port frame by inserting all-thread rods through holes

on the bottom flange on the steel support frame as

shown in Figure 32 and 33, page 21. Secure with

two Ø 2" o.d. x Ø 9/16" i.d. x 0.10" Washers and two

1/2"-13 UNC Nuts.

Floor Sheathing

not shown for

clarity

Metal Base

assembly

exaMPle onlY

2x F

loo

R J

oIs

T

2x F

loo

R J

oIs

T

A35 Brackets

(16 required)

Figure 26 - Floor Joist Installation

Advertising
This manual is related to the following products: