5. Universal Serial Communications

5-5

C

on

ne

ctio

ns

5.

Universal Serial Communications

• A general purpose computer or an ASCII unit of the PLC (master station) controls the POD (slave

station) using dedicated commands.

• The UG230 internal user memory addresses ($u) must be used for memory allocation for switch,

lamp or data display parts.
When the master station specifies a screen number, data is written to the internal memory address
($u) allocated for the screen. If the screen is switched internally, the new screen number is read
and is written to the internal memory address ($u) allocated for the screen.

• For 1 : 1 connection, the UG230 can send an interrupt to the master station through switch

activation, write command from the keypad, and screen change.

• Use MJ2 (or CN1 when the UG230A-DCL is provided) of the UG230 for connection with a

general-purpose computer. Either signal level RS-232C or RS-422 (RS-485) can be selected.

• In addition to 1 : 1 connection, 1 : n connection is available between the general-purpose

computer and the UG230 via RS-422.
(A maximum of 32 UG230 units can be connected.)
For 1 : n connection, interrupts cannot be used.

• For more information, refer to the User’s Manual <PLC Connection> (FEH380).

RESET

disc

MJ2

RS-232C or RS-422 (RS-485)

UG230

Write

General-purpose

computer

Dedicated commands

Interrupt

Read

RESET

disc

MJ2

MJ2

MJ2

MJ2

RS-422 (RS-485) connection

UG230 1

General-purpose computer

UG230 2

UG230 3

UG230 n (n = 1 to 32)