MASTER JET SERIES ATMOSPHERIC GAS FRYERS

CHAPTER 2: INSTALLATION INSTRUCTIONS

2-8

2.4 Connection to Gas Line (cont.)


Gas Connection Pipe Sizes

(Minimum incoming pipe size should be 1-1/2" (38 mm))

Natural

3/4" (19 mm)

1" (25 mm)

1-1/4" (33 mm)

Propane

1/2" (13 mm)

3/4" (19 mm)

1" (25 mm)

Manufactured

1" (25 mm)

1-1/4" (33 mm)

1-1/2" (38 mm)

* For distances of more than 20 feet (6 meters)
and/or more than four fittings or elbows, increase
the connection by one pipe size.

Gas

Single Unit

2 - 3 Units

4 Units*


CE Standard

CE regulations require a combustion air supply of 2m

3

/h per kW per fryer. (See rating plate affixed

to door for kW rating.)




1. Connect the quick-disconnect hose to the fryer quick-disconnect fitting under the front of the

fryer and to the building gas line.

NOTE: Some fryers are configured for a rigid connection to the gas supply line. These units are
connected to the gas supply line at the rear of the unit.

When using thread compound, use very small amounts on male threads only. Use a pipe thread
compound that is not affected by the chemical action of LP gases (Loctite PST567 sealant is one
such compound). DO NOT apply compound to the first two threads. Applying compound to the
first two threads will cause clogging of the burner orifices and control valve.

2. Open the gas-supply valve to the fryer and check all piping, fittings, and gas connections for

leaks. A soap and water solution should be used for this purpose.