INSTALLATION Continued

Gas Connections

All fixed (non mobile) appliances MUST be fitted with a

manual gas cock upstream of the appliance to provide a

means of isolation for servicing or cleaning purposes . A

union or similar means of disconnection must be provided

between the gas cock and the appliance .

A manually operable valve must be fitted to the gas supply

to the kitchen to enable it to be isolated in an emergency .

Whenever practical, this shall be located either outside the

kitchen of near an exit in a readily accessible position .

Where it is not practical to do this, an automatic isolation

valve system shall be fitted which can be operated from a

readily accessible position or near to the exit .

At locations where the manual isolation valve is fitted or

the automatic system can be reset, a notice MUST be fitted

stating:

“ALL DOWNSTREAM BURNER AND PILOT VALVES MUST

BE TURNED OFF PRIOR TO ATTEMPTING TO RESTORE THE

SUPPLY . AFTER EXTENDED SHUT OFF, PURGE BEFORE

RESTORING GAS .”

Before assembly and connection, check gas supply .

A . The type of gas for which the unit is equipped is stamped

on the rating plate located on the lower front panel

simply remove the drip tray for easy access . Connect a

unit stamped “NAT” only to natural gas; connect those

stamped “PRO” only to propane gas .

B . If it is additional equipment or a replacement have a

qualified gas technician check the gas pressure to make

certain that existing gas facilities (meter piping, etc .)

will supply gas to the unit with no more than 1/2” water

column pressure drop .

NOTE: When checking pressure, be sure that all other

equipment on the same gas line is on . A pressure regulator

is supplied with US Range Infra-Red Broilers . The regulator

is preset to deliver gas at the pressure shown on the rating

plate .

C . The appliance and its individual shut off (supplied by

others) must be disconnected from the gas supply piping

system during any pressure testing of that system at

pressures in excess of 1/2” psi (3 .45 kPa) .

D . The appliance must be isolated from the gas supply

piping system by closing its individual manual shut off

valve (supplied by others) during any pressure testing of

the gas supply piping system at test pressures equal to or

less than ½ psi (3 .45 kPa) .

E . The gas supply connection is made either at the top left

rear or lower rear right corner, depending on how the

unit was ordered . A readily accessible approved type of

hand valve should be installed on each supply line . Test

for leaks – DO NOT USE ANY OPEN FLAME .

F . A pressure tap plug is supplied with the units and it is

installed on the manifold . The drip tray must be removed

to use the pressure tap . The gas pressure must be

checked when the unit is installed, to insure that the unit

gas pressure is the same as specified on the rating plate .

If necessary, pressure adjustments must be made at the

supplied pressure regulator .

NOTE: the pressure regulator is located at the top left rear or

bottom right rear of the salamander .

G . If it is a completely new installation, have a qualified gas

technician check meter size and piping to ensure that

the unit is supplied with a sufficient amount of gas at the

specified pressure for unit operation .

H . Make certain that the new piping, joints and connections

have been made in a clean manner and have been

purged, so that the piping compound, chips, etc, will not

clog pilots, valves and/or controls . Use pipe joint sealant

that is resistant to liquefied petroleum gas .

WARNING Check gas connections for leaks . Use a soap

solution or similar means . DO NOT USE AN OPEN FLAME!