Commissioning – Grant Products HPAW155 User Manual
Page 37

Commissioning
33
Notes:
a) Access = 1 is available at all times. To access settings menu with access = 0, remove the front control panel cover then remove
the screw at the base of the BTC. Select the DIP switch 1 to ‘ON’. When the parameters have been set, switch the DIP switch
back to OFF and replace the cover.
b) OUTDR START and BOIL START must always be the same figure.
c) These settings are suitable for a system design of -3˚C to 21˚C. If any other design criteria is used, alter these settings to match
the design.
d) If a buffer or thermal store is being used, change MASS to a suitable setting.
e.g. MASS = 1 (lo) for Monovalent system (no buffer or thermal store)
MASS = 2 (med) for Bivalent system (no buffer or thermal store)
MASS = 3 (Hi) for Bivalent system (with buffer or thermal store)
e) DHW BOIL TARGET of 48˚C assumes the cylinder thermostat setting of 45˚C and thereafter, heated by an auxiliary source – e.g.
immersion element, boiler etc.
f) Pump Delay should be set for about 2 minutes.
g) WWSD should always be set 3˚C higher that the BOIL START setting.
BTC Settings Menu
Item
Access
Active
Mode
Default
Range
OUTDR Start
1
Always
All
21˚C
1 to 29˚C
OUTDR DSGN
1
Always
All
-3˚C
-50 to 0˚C
BOIL START
1
Always
All
21˚C
1 to 65˚C
BOIL DSGN
1
Always
All
48˚C
21 to 104˚C
BOIL MAX
0
Always
All
55˚C
48 to 107˚C, OFF
BOIL MIN
0
Always
All
OFF
OFF, 26 to 82˚C
MASS
0
Always
All
1 (lo)
1(lo)<>2(med)<>3(Hi)
DIFF
0
Always
All
AU
AU, 1 to 23˚C
DHW BOIL TARGET
0
Always
All
48˚C
OFF, 21 to 104˚C
‘pump’ DLY
0
Always
All
20 secs
OFF, 20 secs to 9:55 mins
WWSD (Warm Weather
1
Always
All
24˚C
1 to 38˚C, OFF
Shut Down)
Take a note of these settings and write them in the Commissioning sheet in section 11.4.