Warning – Manitowoc Ice CM MODEL STH003 User Manual

Page 18

Advertising
background image

18

ELECTRICAL REQUIREMENTS
VOLTAGE
The maximum allowable voltage variation is ±10% of
the rated voltage on the ice machine model/serial
number plate at start-up (when the electrical load is
highest).

A qualified electrician must determine proper
wire size dependent upon location, materials
used and length of run (minimum circuit
ampacity can be used to help select the wire
size).

The maximum allowable voltage variation is
±10% of the rated voltage at ice machine
start-up (when the electrical load is highest).

Check all green ground screws in the control
box and verify they are tight before starting
the ice machine.

MINIMUM CIRCUIT AMPACITY
The minimum circuit ampacity is used to help select
the wire size of the electrical supply. (Minimum circuit
ampacity is not the ice machine’s running amp load.)

ELECTRICAL SPECIFICATIONS

WARNING

The ice machine must be grounded in accordance
with national and local electrical code.

Ice

Machine

Voltage

Phase
Cycle

Max. Fuse/

Circuit

Breaker

Minimum

Circuit

Amps

CM50

115/1/60 15

amp 4.1

GFCI REQUIREMENTS

If GFCI (ground fault circuit interrupter) is required by
local electrical code, it must be a breaker type.

Advertising