SUCTION PRESSURE HIGH CHECKLIST

Problem

• Cause

Improper Installation

•

Refer to “Installation/Visual Inspection Checklist”

Discharge Pressure

•

Discharge pressure is too high, and is affecting

suction pressure, refer to “Freeze Cycle Discharge

Pressure High Checklist”

Improper Refrigerant Charge

• Overcharged

•

Wrong type of refrigerant

•

Non Condensable in system

Other

•

Non-Manitowoc components in system

•

Hot gas valve leaking

• Defective

compressor

•

Water inlet valve leaking

SUCTION PRESSURE LOW CHECKLIST

Problem

• Cause

Improper Installation

•

Refer to “Installation/Visual Inspection Checklist”

Discharge Pressure

•

Discharge pressure is too low, and is affecting

suction pressure, refer to “Freeze Cycle Discharge

Pressure Low Checklist”

Improper Refrigerant Charge

• Undercharged

•

Wrong type of refrigerant

Other

•

Non-Manitowoc components in system

•

Improper water supply over evaporator refer to

“Water System Checklist”

•

Loss of heat transfer from tubing on back side of

evaporator

•

Restricted/plugged liquid line drier

•

Restricted/plugged tubing in suction side of

refrigeration system

NOTE: Do not limit your diagnosis to only the items

listed in the checklists.