Important – Manitowoc Ice CM MODEL STH003 User Manual

Page 75

Advertising
background image

75

SYSTEM CONTAMINATION CLEANUP
GENERAL
This section describes the basic requirements for
restoring contaminated systems to reliable service.

IMPORTANT

Manitowoc Ice, Inc. assumes no responsibility for
the use of contaminated refrigerant. Damage
resulting from the use of contaminated refrigerant
is the sole responsibility of the servicing company.

Determining Severity Of Contamination

System contamination is generally caused by either
moisture or residue from compressor burnout entering
the refrigeration system.

Inspection of the refrigerant usually provides the first
indication of system contamination. Obvious moisture
or an acrid odor in the refrigerant indicates
contamination.

If either condition is found, or if contamination is
suspected, use a Total Test Kit from Totaline or a
similar diagnostic tool. These devices sample
refrigerant, eliminating the need to take an oil sample.
Follow the manufacturer’s directions.

If a refrigerant test kit indicates harmful levels of
contamination, or if a test kit is not available, inspect
the compressor oil.

1. Remove the refrigerant charge from the ice

machine.

2. Remove the compressor from the system.
3. Check the odor and appearance of the oil.
4. Inspect open suction and discharge lines at the

compressor for burnout deposits.

5. If no signs of contamination are present, perform

an acid oil test to determine the type of cleanup
required.

Advertising