Mini ECO-i SYSTEM Unit Specifications

1. Outdoor Unit

Unit specifications (B)

MODEL No.

Outdoor Unit

CHX06052

POWER SOURCE

208-230V/1Ǿ/60Hz

PERFORMANCE

Cooling

Heating

Capacity

kW

52,900

60,000

BTU / h

15.5

17.6

Air circulation (Hi)

CFM

3,530

ELECTRICAL RATINGS

Voltage rating

208

230

Available voltage range

187-253

187-253

Running amperes

A

V

V

23.5

21.9

23.5

21.9

A

28.0

28.0

Power input

kW
kW

4.57

4.57

5.72

5.72

4.58

4.58

Max. power input

Max. running amperes *

Power factor

%

93

91

94

91

Max. starting amperes

A

Approx. 1

Approx. 1

Approx. 1

Approx. 1

FEATURES

REFRIGERANT TUBING

Controls

Microprocessor

Defrost control

Rverce cycle, microprocessor control

Sensor temp. recall function

Past service warnings recall function

R410A - 7.7 (3.5)

Refrigerant amount at shipment

Service function

Refrigerant control

Electronic expansion valve

Operation sound (Hi)

dB-A

ft. (m)
ft. (m)

lbs. (kg)

68
52

External finish

Power level
Pressure level

Galvanized steel plate with powder paint

Outdoor unit is higher than indoor unit : 164 (50)

Outdoor unit is lower than indoor unit : 131 (40)

Refrigerant tube
diameter

Liquid tube in. (mm)

3/8 (9.52)

Gas tube

in. (mm)

3/4 (19.05)

Limit of tubing length

492 (150)

Limit of elevation difference
between the 2 units

Refrigerant tubing kit / Joint kit

Optional

Color (Approximate value)

Munsell code 1Y 8.5/0.5

DIMENSIONS & WEIGHT

Unit dimensions

Package dimensions

Unit dimensions

Height

in. (mm)

48-7/16 (1230)

Width

in. (mm)

37 (940)

Depth

in. (mm)

13-13/32 (340)

52-13/32 (1331)
40 (1016)

16-11/32 (415)

Net weight

lbs. (kg)

Shipping weight

lbs. (kg)

Shipping volume

ft

3

(m

3

)

Rated conditions

Colling : Indoor air temperature 80

°

F DB / 67

°

F WB ; Outdoor air temperature 95

°

F DB

*Full-load conditions at Indoor / Outdoor capacity ratio 100%

Colling : Indoor air temperature 89

°

F DB / 73

°

F WB ; Outdoor air temperature 109

°

F DB / 78

°

F WB

Heating : Indoor air temperature 70

°

F DB ; Outdoor air temperature 47

°

F DB / 43

°

F WB

208

230

229 (104)

247 (112)

19.8 (0.56)

05-2311.indd 3