Design of Mini ECO-i SYSTEM

1

2

3

4

5

6

7

8

Checking of limit density

Density limit is determined on the basis of the size

of a room using an indoor unit of minimum capacity.

For instance, when an indoor unit is used in a room

(floor area 80 ft

2

× ceiling height 8.8 ft. = room volume

704 ft.

3

), the graph at right shows that the minimum

room volume should be 497 ft.

3

(floor area 56 ft.

2

) for

refrigerant of 147 oz. Accordingly, openings such as

louvers are required for this room.

<Determination by calculation>

Overall refrigerant charge amount for the air conditioner: oz

(Minimum room volume for indoor unit: ft.

3

)

=

147 (oz) + 123 (oz)

= 0.38 (oz/ft.

3

)

≥≥ 0.3 (oz/ft

3

)

704 (ft

3

)

Therefore, openings such as louvers are required for

this room.

●

Obtain charge amount for each tubing size

Note that the charge amounts per 3.3 ft. are different for each liquid tubing size.

ш3/8" (ш9.52)

→ LA + LB + LC + LD

: 212 ft.

× 0.602 oz/ft. = 127 oz

ш1/4" (ш6.35)

→ 1 + 2 + 3 + 4 + 5 : 75 ft. × 0.279 oz/ft. = 20 oz

Total

147

oz

Additional refrigerant charge amount is 147 oz.

Be sure to check the limit density

for the room in which the indoor

unit is installed.

CAUTION

●

Example of each tubing length

Main tubing Distribution joint tubing

LA = 131 ft.

Indoor side

LB = 16 ft.

1 = 16 ft.

4 = 20 ft.

LC = 16 ft.

2 = 16 ft.

5 = 16 ft.

LD = 49 ft.

3 = 7 ft.

LN

L1
L2

LC

LB

LA

Main tube of unit

1st branch

model 0752

model 0952

model 1252

model 1852

model 1852

Unit distribution tube

1

2

3

n–1

n

Example:

57

114

170

227

284

341

398

454

0

500

1000

1500

2000

2500

3000

3500

4000

400

200

600

800 1000 1200

Total amount of refrigerant

Min.

indoor v

olume

Min.

indoor floor area

(when the ceiling is 8.8 ft.

high)

ft.

3

ft.

2

oz

Range above
the density limit of
0.3 oz/ft.

3

(countermeasures
needed)

Range below
the density limit of
0.3 oz/ft.

3

(countermeasures
not needed)

0 0