Design of Mini ECO-i SYSTEM

1-5. Capacity Correction Graph According to Tubing Length and Elevation Difference

Capacity change characteristics

92 90

88

86

84

82

80

78

76

0

33 66 98 131 164 197 230 262 295 328 361 394 427 459 492

<Cooling>

<Heating>

Ele

vation diff

erence (ft)

Equivalent length (ft)

164

131

98

66

33

0

–33

–66

–98

–131

*1

97

96

95

94

93

92

91

0

33 66 98 131 164 197 230 262 295 328 361 394 427 459 492

164

131

98

66

33

0

–33

–66

–98

–131

Ele

vation diff

erence (ft)

*1

98

99

100

%

Equivalent length (ft)

Base capacity

change rate (%)

Base capacity

change rate (%)

94

100

%

98

96

Inverter model rated performance values

Cooling

Heating

Item

Model

CHX03652
CHX06052

Cooling

capacity

BTU/h(kW)

BTU/h(kW)

BTU/h(kW)

BTU/h(kW)

Power

consumption

Heating

capacity

Power

consumption

38,200 (11.2)
52,900 (15.5)

9,400 (2.76)

15,600 (4.57)

42,700 (12.5)
60,000 (17.6)

9,800 (2.88)

15,600 (4.58)

Outdoor unit heating capacity correction coefficient during frosting/defrosting (1 – (3))

* To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity

found from the capacity graph by the correction coefficient from the table above.

Outdoor intake air –4

5

14

17

21

23

24

28

30

32

33

35

37

39

41

42

temp.

(°F WB RH 85%)

Correction

0.97

0.97

0.97

0.96 0.94

0.91 0.89

0.87

0.87

0.87

0.88

0.89

0.91

0.92 0.95

1.0

coefficient

1. Model Selecting and Capacity Calculator

05-231 Mini ECO-i T_D 2_0116.ind11 11