System design – Sanyo CHX03652 User Manual

Page 24

Advertising
background image

2-16

Design of Mini ECO-i SYSTEM

1

2

3

4

5

6

7

8

Minimum indoor volume & floor area as against
the amount of refrigerant is roughly as given in the
following table.

57

114

170

227

284

341

398

454

511

568

625

682

738

795

852

909

966

1022

1079

1136

0

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

5500

6000

6500

7000

7500

8000

8500

9000

9500

10000

1000

500

1500 2000 2500 3000

Total amount of refrigerant

Min.

indoor v

o

lume

Min.

indoor floor area

(when the ceiling is 8.8 ft.

high)

ft.

3

ft.

2

oz

Range above
the density limit of
0.3 oz/ft.

3

(countermeasures
needed)

Range below
the density limit of
0.3 oz/ft.

3

(countermeasures
not needed)

0

0

CAUTION

Pay special attention to any
location, such as a base-
ment, etc., where leaking
refrigerant can accumulate,
since refrigerant gas is
heavier than air.

Table 2-11 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights

Items

Marks

Contents

Length (ft.)

L1

Max. tubing length

Actual length

492

Equivalent length

574

L (L2 – L3)

Difference between max. length and min.

131

length from the No.1 distribution joint

1

,

2

...

n

Max. length of each distribution tube

98

1

+

2

+...

n-1

Total max. tubing length including length of

656

each distribution tube (only narrow tubing)

H1

When outdoor unit is installed higher than indoor unit

164

When outdoor unit is installed lower than indoor unit

131

H2

Max. difference between indoor units

49

L = Length, H = Height

Allowable tubing
length

>

>

Allowable elevation
difference

>

>

>

>

>

>

+L1

WARNING

Always check the gas den-
sity limit for the room in
which the unit is installed.

2-10. Check of Limit Density

When installing an air conditioner in a room, it is

necessary to ensure that even if the refrigerant gas

accidentally leaks out, its density does not exceed the

limit level for that room.

If the density could exceed the limit level, it is

necessary to provide an opening between the unit

and the adjacent room, or to install mechanical

ventilation which is interlocked with the leak detector.

(Total refrigerant charged amount: oz)

(Min. indoor volume where the indoor unit is installed: ft.

3

)

Limit density 0.3 (oz/ft.

3

)

The limit density of refrigerant which is used in this
unit is 0.3 oz/ft.

3

(ISO 5149).

The shipped outdoor unit comes charged with the

amount of refrigerant fixed for each type, so add it

to the amount that is charged in the field. (For the

refrigerant charge amount at shipment, refer to the

unit’s nameplate.)

2. System Design

Advertising
This manual is related to the following products: