4-56

Mini ECO-i SYSTEM Unit Specifi cations

1

2

3

4

5

6

7

8

5-5. Indoor Fan Performance

5. Concealed Duct High-Static Pressure Type (D Type)

How to Read the Diagram

H

H

M

M

L

883

1059

1236

0

0.40

0.20

0.60

0.80

1.00

H

H,M

M

L

1059

1236

1412

NOTE

Exter

nal Static Pressure

Exter

nal Static Pressure

36 Type

48 Type

(in.WG)

(in.WG)

0

0.40

0.20

0.60

0.80

1.00

Limit line

Limit line

Limit line

Limit line

Air Flow (CFM)

Air Flow (CFM)

H : At shipment

The vertical axis is the External Static Pressure (in.WG) while the horizontal axis represents the Air
Flow (CFM). The characteristic curve for the "H," "Med, " and "Lo " fan speed control.
The nameplate values are shown based on the gH h air flow. Therefore in the case of 36 Type, the
flow is 1059 CFM, while the External Static Pressure is 0.72 in.WG at "H " position. If the external
static pressure is too great (due to long extension of duct, for example), the air flow volume may
drop too low at each air outlet.