Installation instructions – Sanyo CHX03652 User Manual

Page 38

Advertising
background image

2-30

Design of Mini ECO-i SYSTEM

1

2

3

4

5

6

7

8

Reference diagram for snow-proof ducting – 2

Space requirements for setting – (2)

CHX03652/06052

Min. 11-13/16

Min. 11-13/16

Min. 39-3/8

Min. 7-7/8

Min. 59-1/16

Min. 78-3/4

0

Min. 11-13/16

Min.

39-3/8

Min.

7-7/8

Q

Q

Min.

P

Min.

O

(1) Single-unit installation

(2) Obstacles on both sides

[Installation in front-rear rows]

[Obstacles to the front and rear of unit]

The top and both sides must remain open. Either the obstacle to the front or
the obstacle to the rear must be no taller than the height of the outdoor unit.

Dimension Q

The top and both sides must remain open. Either the obstacle to the front or the obstacle

ust be no taller than the height of the outdoor unit.

Outdoor unit

CHX03652/06052

O

P

39-3/8

5-29/32

Dimension Q
If a snow protection duct is attached after the unit is
installed, verify that dimension Q is 19-11/16 in. or more.

If a snow protection duct is
attached after the unit is
installed, verify that dimension
Q is 19-11/16 in. or more.

Unit: in.