Design of Mini ECO-i SYSTEM

Fig. 2-9

Fig. 2-10

Fig. 2-11

3-3. Air Discharge Chamber for Top Discharge

Be sure to install an air discharge chamber in the

field when:

it is difficult to keep a space of min. 20 in. between

the air discharge outlet and an obstacle.

the air discharge outlet is facing a sidewalk and

discharged hot air may annoy passers-by.
Refer to Fig. 2-9.

3-4. Installing the Unit in Heavy Snow Areas

In locations with strong wind, snow-proof ducting

should be fitted and direct exposure to the wind

should be avoided as much as possible.

Countermeasures against snow and wind
In regions with snow and strong wind, the following

problems may occur when the outdoor unit is not

provided with a platform and snow-proof ducting:

a) The outdoor fan may not run and damage to the

unit may occur.

b) There may be no air flow.

c) The tubing may freeze and burst.

d) The condenser pressure may drop because of

strong wind, and the indoor unit may freeze.

3-5. Precautions for Installation in Heavy Snow

Areas

(1) The platform should be higher than the max. snow

depth. (Fig. 2-10)

(2) The 2 anchoring feet of the outdoor unit should

be used for the platform, and the platform should

be installed beneath the air intake side of outdoor

unit.

(3) The platform foundation must be firm and the unit

must be secured with anchor bolts.

(4) In case of installation on a roof subject to strong

wind, countermeasures must be taken to prevent

the unit from being blown over.

Air discharge

In regions with significant snowfall, the outdoor unit should
be provided with a platform and snow-proof duct.

Without snow-
proof ducting
(Low platform)

With snow-
proof ducting
(High platform)

Outdoor

Duct

Air

Unit

intake