Design of Mini ECO-i SYSTEM

2-7. Additional Refrigerant Charge

Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.

Table 2-8 Amount of Refrigerant Charge Per Meter, According to Liquid Tubing Size

Liquid tubing size

Amount of refrigerant

(in. (mm))

charge (oz/ft.)

ш1/4”

(ш6.35)

0.279

ш3/8” (ш9.52)

0.602

Required amount of charge = (Amount of refrigerant

charge per meter of each size of liquid tube × its tube

length) + (...) + (...)

*Always charge accurately using a scale for weighing.

Table 2-9 Refrigerant Charge Amount at Shipment (for outdoor unit)

2-8. System Limitations

Table 2-10 System Limitations

Number of max. connectable indoor units

Outdoor units (Type)

CHX03652

6

CHX06052

9

Max. allowable indoor/outdoor capacity ratio

50 130%

Heat pump unit

(Single-phase)(oz)

CHX03652

123

CHX06052

123

2-9. Tubing Length

R410A distribution joint
APR-P160BA (for indoor unit)

Note: Do not use commercially available T-joints for the liquid tubing.

H2

LD

L1
L2

LC

LB

LA

* Be sure to use special R410A distribution joints (APR: purchased separately) for outdoor
unit connections and tubing branches.

Main tube of unit

1st branch

Unit distribution tube

1

2

3

n-1

n

L3

H1

Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown
in the figure below.

2. System Design