Installation standards – Sanyo CHX03652 User Manual

Page 210

Advertising
background image

5-22

Test Run and Others

1

2

3

4

5

6

7

8

2. The standards for minimum room volume are as

fol-lows.

(1) No partition (shaded portion)

(2) When there is an effective opening with the

adjacent room for ventilation of leaking refrigerant
gas (opening without a door, or an opening 0.15%
or larger than the respective floor spaces at the
top or bottom of the door).

(3) If an indoor unit is installed in each partitioned

room and the refrigerant tubing is interconnected,
the smallest room of course becomes the object.
But when mechanical ventilation is installed
interlocked with a gas leakage detector in the
smallest room where the density limit is exceeded,
the volume of the next smallest room becomes the
object.

3. The minimum indoor floor space compared with the

amount of refrigerant is roughly as follows (when
the ceiling is 8.8 ft. high):

4-1. Check of Density Limit

The room in which the air conditioner is to be
installed requires a design that in the event of
refrigerant gas leaking out, its density will not
exceed a set limit.
The refrigerant (R410A), which is used in the air
conditioner, is safe, without the toxicity or combustibility of
ammonia, and is not restricted by laws imposed to protect
the ozone layer. However, since it contains more than air,
it poses the risk of suffocation if its density should rise
excessively.
Suffocation from leakage of refrigerant is almost non-
exis-tent. With the recent increase in the number of high
density buildings, however, the installation of multi air
conditioner systems is on the increase because of the
need for effective use of floor space, individual control,
energy conservation by curtailing heat and carrying
power, etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared to
conventional individual air conditioners. If a single unit
of the multi air conditioner system is to be installed in
a small room, select a suitable model and installation
procedure so that if the refrigerant accidentally leaks out,
its density does not reach the limit (and in the event of
an emergency, measures can be made before injury can
occur).
In a room where the density may exceed the limit, create
an opening with adjacent rooms, or install mechanical
ventilation combined with a gas leak detection device.
The density is as given below.

Total amount of refrigerant (oz)

Min. volume of the indoor unit installed room (ft.

3

)

≤≤ Density limit (oz/ft.

3

)

The density limit of refrigerant which is used in multi air

conditioners is 0.3 oz/ft

3

(ISO 5149).

NOTE

1. If there are 2 or more refrigerating systems in a

single refrigerating device, the amount of refrigerant
should be as charged in each independent device.

For the amount of charge in this example:

The possible amount of leaked refrigerant gas in rooms A,
B and C is 353 oz.

The possible amount of leaked refrigerant gas in rooms D,
E and F is 529 oz.

Outdoor unit

Refrigerant tubing

Indoor unit

e.g., charged
amount (353 oz)

Outdoor unit

Indoor unit

Room A Room B Room C Room D Room E Room F

e.g., charged

amount (529 oz)

Refrigerant tubing

Outdoor unit

Very
small
room

Indoor unit

Small
room

Medium
room

Large room

Mechanical ventilation device Ð Gas leak detector

0

0

57

114

170

227

284

341

398

454

0

500

1000

1500

2000

2500

3000

3500

4000

400

200

600

800 1000 1200

Total amount of refrigerant

Min.

indoor v

o

lume

Min.

indoor floor area

(when the ceiling is 8.8 ft.

high)

ft.

3

ft.

2

oz

Range above
the density limit of
0.3 oz/ft.

3

(countermeasures
needed)

Range below
the density limit of
0.3 oz/ft.

3

(countermeasures
not needed)

4. Installation Standards