Td831137-02_5g, System controller – Sanyo CHX03652 User Manual

Page 82

Advertising
background image

3-38

Control of Mini ECO-i SYSTEM

1

2

3

4

5

6

7

8

4. System Controller

System controller / SHA-KC64UG

●

Example of central control with system controller (individually controlled)

New control wiring system (S-net link system)

●

New control wiring system (S-net) allows connection of as many as total of 94 units (64 Indoor unit

+30 Outdoor unit) to a single contorl line (non-polar twin-line main bus).

●

The main bus is twin-core and non-polar for easier wiring.

●

Using concurrently as remote controller, system controller can control maximum up to 64 indoor units (or

groups) individually.

●

The system without remote controller can be formed.

●

Maximum up to 2 system controllers (1 main, 1 sub) can be installed.

●

It can separate the 64 indoor units into 4 zones and control each zone individually.

●

Maximum up to 16 groups can be registered to each zone.

●

Collective control and individual group (unit) control can be performed also.

●

Alarm and operation output for an external collected signal is available (potential free contact) DC24V

Max. 1A.

●

Input terminal for collective operation on / off is available.

Outdoor unit

Remote
controller

System
controller
(main)

System without
Remote controller

Group
control

Outdoor unit

2157_M_I

System
controller
(sub)

Remote
controller

Group
control

Group
control

Remote
controller

Advertising
This manual is related to the following products: