7. INSTALLATION INSTRUCTIONS

7-1. Installation Site Selection

7-1-1. Indoor Unit

WARNING

To prevent abnormal heat

generation and the possibility

of fire, do not place obsta-

cles, enclosures and grilles

in front of or surrounding the

air conditioner in a way that

may block air flow.

Max. Allowable Tubing

Limit of Tubing

Limit of Elevation

Required Amount of

Length at Shipment

Length (L)

Difference (H)

Additional Refrigerant

Model

(ft.)

(ft.)

(ft.)

(oz./ft.)

*

25

50

23

a) 0.16

9,000 BTU

25

65

23

b) 0.27

12,000/18,000 BTU

*

If total tubing length becomes a) 25 to 50 ft. (max.), b) 25 to 65 ft. (max.) charge additional refrigerant (R22) by a) 0.16 oz./ft., b) 0.27 oz./ft.
No additional compressor oil is necessary.

Drain hose

Indoor unit

Outside drainage

Fig. 1

*

6" (15 cm) min.

Front View

2" (5 cm) min.

*

6" (15 cm) min.

*

KS1852 only

2" (5 cm) min.

*

6" (15 cm) min.

2" (5 cm) min.

Fig. 2

INDOOR
UNIT

Tubing length (L)

OUTDOOR
UNIT

Elevation
difference (H)

Fig. 3a

Indoor unit

Floor level

Wall

Minimum height

from floor level

5 ft. (1.5 m)

Fig. 3b

For stable operation of the

air conditioner, do not

install wall-mounted type

indoor units under 5 ft.

(1.5 m) from floor level.

CAUTION

Table 1

AVOID:

direct sunlight.

nearby heat sources that may affect performance of

the unit.

areas where leakage of flammable gas may be

expected.

places where large amounts of oil mist exist.

DO:

select an appropriate position from which every cor-

ner of the room can be uniformly cooled. (High on a

wall is best.)

select a location that will hold the weight of the unit.

select a location where tubing and drain hose have

the shortest run to the outside. (Fig. 1)

allow room for operation and maintenance as well as

unrestricted air flow around the unit. (Fig. 2)

install the unit within the maximum elevation differ-

ence (H) above the outdoor unit and within a total

tubing length (L) from the outdoor unit as detailed in

Table 1 and Fig. 3a.