8-2. Dry Operation (Dehumidification)

Dry operation uses the ability of the cooling cycle to remove moisture from the air, but by running at low

level to dehumidify without greatly reducing the room temperature. The air conditioner repeats the cycle of

turning ON and OFF automatically as shown in the chart below according to the room temperature.

Intermittent ventilation occurs by switching the indoor fan speed between L

«

LL.

Dry operation does not occur when the room temperature is under 59°F, which is the Monitor Zone.

When the compressor stops, the indoor fan stops as well.

8-3. Freeze Prevention

This function prevents freezing of the indoor heat exchange coil.

When the compressor has been running for 10 minutes or more and the temperature of the indoor heat

exchange coil falls below –2°F, the control circuit stops the compressor for at least 6 minutes. The com-

pressor does not start again until the temperature rises above 46°F or 6 minutes have elapsed.

NOTE

Room temp.

T + 4

¡

F

T – 2

¡

F

Room temp.

59

¡

F

Set temp. T

¡

F

Cooling operation

*

Dry A Zone

Compressor:

Continuous operation

FMI (indoor fan): L (low speed)/LL (very low speed) intermittent ventilation only while the compressor is ON.

*

Dry B Zone

Compressor:

Intermittent operation (ON for 3 minutes and OFF for 9 minutes)

FMI (indoor fan): L (low speed)/LL (very low speed) intermittent ventilation only while the compressor is ON.

Monitor Zone

Both the indoor and outdoor units stop.

Set temp.

T+4

¡

F

Room temp.

More than

6 minutes

Indoor fan

6 minutes

T

¡

F

ON

ON

Compressor

OFF

OFF

Set speed

Set speed

ON

ON

More than

10 minutes

More than

10 minutes

Thermo OFF

Thermo ON

34

¡

F

*

Indoor heat exch.
coil temp.

*

KS1852: 36

¡

F