9-2. Air Conditioner Does Not Operate

9-2-1. Circuit breaker trips (or fuse blows)

A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.)

●

There is a possibility of ground fault.

●

Check insulation resistance.

If resistance value is 1M

½

or less, insulation is defective (“NO”).

B. Circuit breaker trips in several minutes after turning the air conditioner on.

●

There is a possibility of short circuit.

1

Indoor

unit

Ground

1

2

Outdoor

unit

2

1

5

Circuit
breaker

4

5

4

1

2

Power
supply

Inter-unit
power wiring

Measure insulation
resistance of electrical
parts in outdoor unit.

NO

NO

Set circuit breaker to OFF.

*

Measure insulation
resistance of electrical
parts in indoor unit.

1

Remove both power supply wires
and inter-unit wires from terminal
plate in outdoor unit.
Measure insulation resistance
of outdoor unit.

•

2

Remove inter-unit wires from
terminal plate in indoor unit.
Measure insulation resistance
of indoor unit.

•

•

•

Insulation of
outdoor unit
is defective.

Insulation of
indoor unit
is defective.

WARNING

Check capacity of circuit breaker.

Capacity of circuit breaker is
suitable.

•

Replace with suitable
one (larger capacity).

•

Measure resistance of compressor
motor winding.

•

Measure resistance of outdoor fan
motor winding.

•

NO