Sanyo CL1852 User Manual

Page 53

Advertising
background image

50

9-3-3. Only compressor does not run

9-3-4. Only flap motor does not run

9-3-5. Function of outdoor fan speed control does not work properly

Measure resistance of
compressor motor winding.

•

Measure power supply
voltage.
The voltage is too low.

•

NO

Check compressor motor
capacitor.

•

Either internal protector or
overload relay is working.

•

Temperature of compressor
is abnormally high.

•

YES

YES

YES

NO

Refrigerant gas shortage.

Charge refrigerant gas (R22).

Rotor may be locked up.

Measure resistance of flap
motor winding. (FLP)

•

Check thermostat in outdoor unit.
(23S)

•

Refer to “8-4. Outdoor Fan Speed Control.”