9-3-3. Only compressor does not run
9-3-4. Only flap motor does not run
9-3-5. Function of outdoor fan speed control does not work properly
Measure resistance of
compressor motor winding.
•
Measure power supply
voltage.
The voltage is too low.
•
NO
Check compressor motor
capacitor.
•
Either internal protector or
overload relay is working.
•
Temperature of compressor
is abnormally high.
•
YES
YES
YES
NO
Refrigerant gas shortage.
Charge refrigerant gas (R22).
Rotor may be locked up.
Measure resistance of flap
motor winding. (FLP)
•
Check thermostat in outdoor unit.
(23S)
•
Refer to “8-4. Outdoor Fan Speed Control.”