8-4. Outdoor Fan Speed Control (CL

´´´´

models only)

Low ambient fan speed control

●

This function protects the compressor from being damaged due to flowback of the liquid refrigerant to the

compressor when the outdoor temperature is very low.

●

When the air temp. thermistor (TH) on the outdoor units detects a change in temperature, the controller on

the electrical component box activates to control the fanspeed automatically.

●

If the outdoor temperature falls below 57°F, the fan speed switches to MED.

●

If the outdoor temperature falls below 30°F, the fan speed switches to LOW.

*1 Regardless of outdoor temperature, outdoor fan motor operates at first at HIGH speed for 23 ± 5 sec-

onds to give the motor an initial boost.

*2 When the fan speed switches, the controller terminal’s location where line voltage comes out (

●

●

–

●

●

)

shifts accordingly.

57

¡

F

30

¡

F

Outdoor

temperature

Fan speed

*

1

Fan motor output

*

2

(Line voltage 115V or 230V)

HIGH

MEDIUM

LOW

➀

–

➅

(WHT–BRN)

➁

–

➅

(VLT–BRN)

➂

–

➅

(YEL–BRN)