INSTALLATION

A-7

A-7

IDEALARC CV-400

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Master TOC

Retur

n to Master TOC

Retur

n to Master TOC

Retur

n to Master TOC

2

1

+

-

FIGURE A.5

OUTPUT TERMINAL CONNECTIONS

1. NEGATIVE (-) WELDING CABLE CONNECTION

2. POSITIVE (+) WELDING CABLE CONNECTION

TABLE A.1 - CABLE SIZES FOR COMBINED LENGTH

OF ELECTRODE AND WORK CABLE

MACHINE LOAD

400A

500A

(100% DUTY

(50% DUTY

CABLE LENGTHS

CYCLE)

CYCLE)

UP TO 50 ft

3/0

2/0

(15 m)

85 mm

2

67 mm

2

50 to 100 ft

3/0

2/0

(15 to 30 m)

85 mm

2

67 mm

2

100 to 150 ft

3/0

3/0

(30 to 46 m)

85 mm

2

85 mm

2

150 to 200 ft

3/0

3/0

(46 to 61 m)

85 mm

2

85 mm

2

200 to 250 ft

4/0

4/0

(67 to 76 m)

107 mm

2

107 mm

2