TROUBLESHOOTING & REPAIR

F-14

F-14

IDEALARC CV-400

INPUT CONTACTOR TEST

(continued)

FIGURE F.3 – INPUT CONTACTOR CONNECTIONS

X1, #232

#233

TEST PROCEDURE

1. Disconnect the main input supply power to

the machine.

2. With the 5/16” nut driver, remove the case

top and the reconnect panel cover.

3. Locate the two leads connected to the input

contactor coil, #233 and X1 #232 (top). See
Figure F.3 for location.

4. Connect an AC voltmeter to the leads.

Electric Shock can kill.

• With the input power on, there

are high voltages inside the
machine.

Do not reach into

the machine or touch any
internal part of the machine
while the power is on.

5. Apply the correct voltage to the machine and

turn the power switch (S1) ON.

6. Check for 120VAC at the contactor coil leads.

If the 120VAC is NOT present, with the power
switch (S1) on, check the power switch (S1)
and associated circuitry.

See the Wiring

Diagram.

Also perform the Control

Transformer (T2) Voltage Test.

If the 120VAC is present and the contactor
does NOT activate, then the input contactor is
faulty. Replace the input contactor.

WARNING