Installation

6

2.5

Piping Considerations

Consideration should be given before installing refrigerant and liquid lines next to, under or above

electronic equipment.

2.5.1 Drain Line

A 3/4" (19.1 mm) female pipe thread (FPT) connection is provided for the evaporator coil condensate

drain. This drain line also drains the humidifier, if applicable. The drain line must be located so it will

not be exposed to freezing temperatures. The drain should be at least the full size of the drain connec-

tion and pitched a minimum of 1/8" per ft. (11 mm per meter).

NOTE
This line may contain boiling water. Select appropriate drain system materials.
The Challenger ITR comes standard with a condensate pump will require a field-supplied trap

downstream from the pump. The drain line must comply with all applicable codes.

Table 2

Piping connection size

Air-Cooled Unit Connection Sizes—in.

Model No. BR/BM

60Hz (50Hz)

Liquid Line O.D. Copper

L

Hot Gas Line O.D. Copper

HG

067A (065A)

1/2

7/8

Split System Fan Coil Unit Connection Sizes—in.

Model No. BR/BM

60Hz (50 Hz)

Liquid Line

L

Suction Line

SC

060E (059E)

1/2 O.D. Cu

1-1/8 O.D. Cu

All Units: Connection Sizes—in.

Humidifier Line

O.D. Copper

H

Condensate

Drain Line

C

Condensate Pump Line

O.D. Copper

P

Hot Water Reheat

O.D. Copper

1/4

1/2 OD Cu

1/2

Supply HWS

Return HWR

5/8

5/8

Water/Glycol-Cooled Unit Connection Sizes—in.

Model No. BR/BM

60Hz (50 Hz)

Supply Line

S

Return Line

R

071WG (070WG)

1-1/8

1-1/8

GLYCOOL Unit Connection Sizes —in.

Model No. BR/BM

60Hz (50 Hz)

Supply Line

S

Return Line

R

061G (058G)

1-1/8

1-1/8

Chilled Water Unit Connection Sizes—in.

Model No. BR/BM

60Hz (50 Hz)

Supply Line

CWS

Return Line

CWR

102C (101C)

1-1/8

1-1/8