0 split system models, 1 location considerations, 1 air-cooled condensing units – Liebert Challenger ITR User Manual

Page 44: 2 water/glycol-cooled condensing units, 2 electrical connections, 1 line voltage, 2 low voltage, Plit, Ystem, Odels

Advertising
background image

Split System Models

38

7.0

S

PLIT

S

YSTEM

M

ODELS

Three (3) condensing unit styles are available: two (2) air-cooled and one (1) water/glycol-cooled con-

densing unit.

7.1

Location Considerations

7.1.1 Air-Cooled Condensing Units

To assure an adequate air supply, it is recommended that all condensing units be located in a clean

air area, away from loose dirt and foreign matter that may clog the coil.
Condensing units must not be located in the vicinity of steam, hot air, or fume exhausts or closer than

18" from a wall, obstruction, or adjacent unit.
The outdoor condensing unit should be located for maximum security and maintenance accessibility.

Avoid ground-level sites with public access or areas that will contribute to heavy snow accumulations.

Do not allow the discharge air to blow into another condensing unit.
A solid base, capable of supporting the weight of the condenser and at least 2" (51 mm) higher than

the surrounding grade and at least 2" (51 mm) larger than the condensing unit base dimensions,

should be installed at the pre-determined location. In snow areas, a base of sufficient height to clear

snow accumulation must be installed.
The centrifugal fan air-cooled condensing unit may be located above the dropped ceiling or any remote

indoor area. If noise is of concern, the condensing unit should be located away from personnel. Normal

operating sound may be objectionable if the condensing unit is placed near quiet work areas.
To mount the unit in the ceiling, refer to 7.5.1 - Installing the Indoor Condensing Unit for hang-

ing guidelines and to Figure 23 - Detail of ceiling hanging bracket for dimensional data.

7.1.2 Water/Glycol-Cooled Condensing Units

The condensing unit may be located above the dropped ceiling or any remote indoor area. If noise is of

concern, the condensing unit should be located away from personnel. Normal operating sound may be

objectionable if the condensing unit is placed near quiet work areas. To mount the unit the in ceiling,

refer to 7.5.1 - Installing the Indoor Condensing Unit.

7.2

Electrical Connections

Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to elec-

trical schematic when making connections. Make all wiring and electrical connections in accordance

with local and national codes.

7.2.1 Line Voltage

Line voltage electrical service is required for all condensing units at the location of the condensing

unit. This power supply does not have to be the same voltage as the indoor unit. This separate power

source may be 208, 230, 460 or 575V, 60 Hz; or 200, 230, or 380/415V, 50 Hz. A disconnect switch is

required and must be mounted per local and national codes to isolate the unit for maintenance.

7.2.2 Low Voltage

The control cable between the condensing unit and the evaporator unit is connected between termi-

nals 1,2 and 3 on the terminal strip in the evaporator unit and the condensing unit control box. A

fourth wire is required on systems with hot gas bypass. NEC Class 1 wiring is required. Glycol-cooled

units also require a two-wire control connection to the drycooler and pump package.

!

WARNING

Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power before working within the unit. Use a

voltmeter to make sure power is turned off before making any electrical connections.

Advertising