Glycol/GLYCOOL-Cooled Models

29

5.5

Filling Instructions

5.5.1 Preparing the System for Filling

It is important to remove any dirt, oil or metal filings that may contaminate the cooling system piping

in order to prevent contamination of the fresh glycol solution and fouling of the drycooler piping. The

system should be flushed thoroughly using a mild cleaning solution or high-quality water and then

completely drained before charging with glycol. Cleaning new systems is just as important as clean-

ing old ones. New systems can be coated with oil or a protective film; dirt and scale are also common.

Any residual contaminants could adversely affect the heat transfer stability and performance of your

system. In many cases, in both old and new systems, special cleaners are needed to remove scale, rust

and hydrocarbon foulants from pipes, manifolds and passages. Clean heat transfer surfaces are

important in maintaining the integrity of the heating/cooling system. For more information on clean-

ers and degreasers, contact your sales representative. Follow the manufacturer's instructions when

using these products.
Calculate the internal volume of the system as closely as possible. See Table 12 and Table 14 for

unit volumes. Use volume in Table 13 for glycol piping volumes.

Table 12

Indoor unit glycol volume approximate gallons (liters) max.

Model (50 Hz)

Glycol-Cooled

GLYCOOL

071WG/(070WG)

2.0 (7.5)

061G/(058G)

4.0 (15.1)

Table 13

Volume in standard Type “L” copper piping

Diameter (in.)

Volume

Outside

Inside

Gal/Ft L/M

1/2

0.123

0.008 (0.01)

5/8

0.555

0.012 (0.15)

3/4

0.666

0.018 (0.22)

7/8

0.785

0.025 (0.31)

1-1/8

1.025

0.043 (0.53)