6 condenser, 7 glycol regulating valve, 1 glycol regulating valve adjustment – Liebert Challenger ITR User Manual

Page 42: 2 testing valve function, Table 18 refrigerant control settings psi (kpa), Condenser, Glycol regulating valve, Glycol regulating valve adjustment, Testing valve function, Table 18

Advertising
background image

Glycol/GLYCOOL-Cooled Models

36

5.6

Condenser

The condenser is designed to operate in conjunction with a drycooler. The maximum coolant pressure

is 350 psig (2413 kPa).

5.7

Glycol Regulating Valve

The glycol regulating valve automatically regulates the amount of coolant necessary to remove the

heat from the refrigeration system, permitting more fluid to flow when load conditions are high and

less fluid to flow when load conditions are low. The valve consists of a brass body, balance spring,

valve seat, valve disc holders, capillary tube to discharge pressure, and adjusting screw.

5.7.1

Glycol

Regulating Valve Adjustment

The Liebert Challenger ITR may be equipped with either a standard Johnson Controls valve, 150 psig

(1034 kPa) or with a high-pressure Johnson Controls valve, 350 psig (2413 kPa). For details on adjust-

ing the valve, refer to 4.3.1 - Water Regulating Valve Adjustment.

5.7.2 Testing Valve Function

When the refrigeration system has been off for approximately 10-15 minutes, the coolant flow should

stop.
Should the coolant continue to flow, the valve is either improperly adjusted or the pressure sensing

capillary is not connected properly to the condenser.

NOTE
For pressures above 150 psig (1034 kPa), the high pressure option for high pressure valve(s)

is required.

Table 18

Refrigerant control settings psi (kPa)

Low Pressure

Cut Out

Low Pressure

Cut In

High Pressure

Cut Out

20 (137.9)

65 (448.2)

360 (2482)