Air-Cooled Models

14

3.0

A

IR

-C

OOLED

M

ODELS

3.1

Condenser Location

The air-cooled condenser should be located for maximum security and maintenance accessibility.

Avoid ground level sites with public access or areas that contribute to heavy snow or ice accumula-

tions. Utilize centrifugal condensers whenever interior building locations must by used. To assure

adequate air supply, it is recommended that condensers be located in a clean air area, away from

loose dirt and foreign matter that may clog the coil. In addition, condensers should not be located in

the vicinity of steam, hot air, or fume exhausts. Also, condensers should be located no closer than

three feet (1 meter) from a wall, obstruction, or adjacent unit.
Install condensers in a level position to assure proper refrigerant flow and oil return. For roof instal-

lation, mount condensers on steel supports in accordance with local codes. To minimize sound and

vibration transmission, mount steel supports across load bearing walls. For ground installation, a

concrete pad will provide adequate support. Condenser legs have mounting holes for securing the con-

denser to the steel supports or concrete pad.

3.2

Electrical Connections

Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to elec-

trical schematic when making connections. Make all wiring and electrical connection in accordance

with local and national codes.

3.2.1 Line Voltage

Line voltage electrical service is required for all air-cooled condensers at the location of the condenser.

This power supply does not have to be the same voltage as the indoor unit. This separate power source

may be 208, 230, 460, or 575 V, 60 Hz; or 200, 230, or 380/415 V, 50 Hz. The disconnect switch may be

factory-supplied and mounted in the electrical panel or field-supplied and mounted per local and

national codes.

3.2.2 Low Voltage

A control interlock between the condenser and the indoor unit is required and is connected between

70 and 71 in the handy box of the indoor unit and the electric panel of the air-cooled condenser. NEC

Class 1 wiring is required.

3.2.3 Lee-Temp/Flood Back Head Pressure Control Condensers

Lee-Temp condensers require a separate power supply for the heated receivers. This power supply is

connected to the electrical connection box on the end of the receiver.

!

WARNING

Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power before working within the unit. Use a voltmeter

to make sure power is turned off before making any electrical connections.