0 chilled water models, 1 piping considerations, Hilled – Liebert Challenger ITR User Manual

Page 43: Ater, Odels, Piping considerations

Advertising
background image

Chilled Water Models

37

6.0

C

HILLED

W

ATER

M

ODELS

6.1

Piping Considerations

Manual shut-off valves should be installed at the supply and return lines to each unit. This will pro-

vide for routine service and emergency isolation of the unit.
Consideration of the minimum water temperature to be supplied from the chiller will determine if the

need exists to insulate supply and return lines. Insulation will prevent condensation on the supply

and return lines.
To provide for the emergency of water leaks and the consequences of sub-floor flooding, floor drains

should be provided with wet traps or a water detection system, such as a Liqui-tect, that is installed

near the base of the unit or below the elevated floor.

Figure 18 Chilled water general arrangement - horizontal flow (BR)

A

B

AB

FIELD PIPING

SL-11899
Pg. 5

Air
Flow

Chilled
Water
Coil

Bleed
Valve

Valve
Actuator

Valve

Flow
Switch
(optional)

Chilled
Water
Supply

Chilled
Water
Return

Hose
Bibs*

Hose
Bibs*

Shutoff
Valves*

3-WAY VALVE

Air
Flow

Bleed
Valve

Chilled
Water
Coil

Valve
Actuator

Shutoff
Valves*

Chilled
Water
Return

Chilled
Water
Supply

2-WAY VALVE

2-Way
Chilled
Water
Valve

SINGLE CIRCUIT SHOWN

*Components are not supplied by Emerson but
are recommended for proper circuit operation
and maintenance.

FACTORY PIPING

3-Way

Chilled

Water

Advertising