Installation

11

2.6

Electrical Connections

Three-phase electrical service is required for all models in either 208, 230, 460, or 575 V, 60 Hz; or

200, 230, or 380/415 V, 50 Hz. Electrical service shall conform to national and local electrical codes.

Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to elec-

trical schematic when making connections.
A manual electrical disconnect switch should be installed within 5 feet (1.6 m) of the Liebert Chal-

lenger ITR in accordance with codes. A factory-supplied, locking disconnect switch is factory-mounted

within the unit behind the front door.

NOTICE

Three-phase power must be connected to the Liebert Challenger ITR line voltage terminals in

the proper sequence so that scroll the compressor rotates in the proper direction.

Figure 8

Electrical connections

1. Electric conduit knockouts on top and bottom of electric box. Knockout size 1-3/4" (44.5mm).

2. Three phase connection. Electric service connection terminals when factory disconnect switch

is supplied.

3. Factory-installed locking disconnect switch.
4. Three-phase electric service not by Liebert.
5. Earth ground connection (50/60Hz). Connection terminal for field-supplied earth grounding wire.
6. Earth ground bar (50Hz only). Connection terminals with factory ground from each high

voltage component for field supplied earth grounding wire.

7. Control and monitoring section of electric box.
8. Remote unit shutdown. Replace existing jumper between Terminals 37 + 38 with normally

closed switch having a minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring. Two

additional contact pairs available as an option (labeled as 37B & 38B, 37C & 38C). Replace

existing jumper for appropriate pair as done for 37 & 38.

!

WARNING

Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power before working within the unit. Use a voltmeter

to make sure power is turned off before making any electrical connections.

75 76 82 83 84 85 88 89 91 92 93 94 95 96 97 1

37C 38C 37B

37 38

24 50 51 55 56

77 78

4

7

2

3

4

5

71

70

15

6

11

13

12

17

16

14

13

10

9

8

8

9

1

1

2

3

38B

Terminal Block*
(for customer connections)

Electrical Handy Box*
(factory-installed with cover)

DPN001524
REV 0

Advertising