Table 19 unit refrigerant charge, Table 22 line coupling sizes, Table 19 – Liebert Challenger ITR User Manual

Page 46: Unit refrigerant charge, Table 20, Table 21, Table 22, Line coupling sizes

Advertising
background image

Split System Models

40

Once all piping is complete, check for leaks and dehydrate the field piping as follows:
1. Pressurize the field piping to 150 PSIG (1034 kPa) using dry nitrogen with a trace of refrigerant.

Check system for leaks with a suitable leak detector.

2. After completion of leak testing, release the test pressure (per local code) and pull a deep vacuum

on the field piping with a suitable pump.

3. After 15 minutes, check the pressure readings and, if they have not changed, break vacuum with

dry nitrogen. Pull a second vacuum to 250 microns or less. Recheck the pressure after 15 minutes.

Table 19

Unit refrigerant charge

Model

R22 Charge

R407C Charge

Model

R22 Charge

R407C Charge

lb (kg)

lb (kg)

lb (kg)

lb (kg)

060E

0.81 (0.37)

0.8 (0.4)

PF_Z67A-_L

51.69 (23.45)

50.1 (22.7)

059E

0.81 (0.37)

0.8 (0.4)

PF_Z66A-_L

51.69 (23.45)

50.1 (22.7)

MC_65/64A

27.00 (12.25)

26.1 (11.8)

PF_067A-_H

51.69 (23.45)

50.1 (22.7)

PF_067A-_L

26.63 (12.08)

25.8 (11.7)

PF_066A-_H

51.69 (23.45)

50.1 (22.7)

PF_066A-_L

26.63 (12.08)

25.8 (11.7)

MC_69/68W

5.88 (2.67)

n/a

Table 20

Line charges - refrigerant per 100 ft (30 m) of Type “L” copper tube

O.D.

R22

R407C

Liquid Line

lb (kg)

Suction Line

lb (kg)

Liquid Line

lb (kg)

Suction Line

lb (kg)

1/2"

7.3 (3.3)

0.2 (0.1)

6.9 (2.9)

-

5/8"

11.7 (5.3)

0.3 (0.2)

11.0 (4.6)

0.4 (0.2)

7/8"

24.4 (11.1)

0.7 (0.3)

23.0 (9.6)

1.0 (0.4)

1-1/8"

41.6 (18.9)

1.2 (0.6)

39.3 (16.3)

1.7 (0.7)

1-3/8"

63.3 (28.7)

1.9 (0.8)

59.8 (24.8)

2.7 (1.1)

Table 21

Recommended refrigerant lines (R22 or R407C) sizes OD copper

Equivalent Feet (m)

3.5 Tons

036E (035E)

23 & 33 kW

060E (059E)

Suction

Liquid

Suction

Liquid

0-50 (0-15)

7/8"

1/2"

1-1/8"

1/2"

51-100 (16-30)

1-1/8"

1/2"

1-1/8"

5/8"

101-150 (31-45)

1-1/8"

5/8"

1-3/8"

5/8"

Table 22

Line coupling sizes

Line Size

OD Cu, in.

Coupling

Size

Torque

lb-ft.

1/2 & 5/8

#10

35-45

1-1/8

#12

50-65

Advertising