Chapter 4. FUNCTION BLOCK

4 - 2

4.2.1 Module Initialization
1) G3F-AD3A, G4F-AD3A

Module Initialization function block is used in a program with setting of A/D conversion module located
base number, slot number of located module on base, specifying a channel enable, analog input data
type and the information of average processing.

Function

block

I/O

Variable

Data

type

Descriptions

REQ

BOOL

Function Block Execution Request Area

- The execution of function block initialization is requested in this area.

- If the status of condition connected with this area is changed from low(0) to high(1),

function block initialization for the module is executed.

BASE

USINT

Base Location Number Area

- The base No. on which A/D conversion module is mounted is written on this area.

- Setting range : 0 to 3

SLOT

USINT

Slot Location Number Area

- The slot No. on which A/D conversion module is mounted is written on this area.

- Setting range: 0 to 7

CH

BOOL[8]

Available Channel Specification Area

- Enabled channels are specified to 1 and disabled channels are specified to 0.

TYPE

BOOL[8]

Analog Input Data Type Specification Area

- Output digital data type for each channel is specified in this area.

- 0 is for the range of 1 ~ 5VDC and DC4 ~ 20mA.

- 1 is for the range of 0 ~ 10VDC

AVG_

EN

BOOL[8]

Enable / Disable of Average processing

- 0 is for the sampling processing.

- 1 is for the average processing of the number of times.

Input

AVG_

NUM

USINT

[8]

Set a constant of the average processing of the number of times.

- Setting range : 2 ~ 255

DONE

BOOL

Function Block Execution Complete Area

- When function block initialization is executed with no error, 1 is written and until

next execution, 1 is continuing. When error occurs, 0 is written and operation come

to stop.

STAT

USINT

Error Code Display Area

- When error occurs during function block initialization, the error code number is

written.

Output

ACT

BOOL[8]

Channel Operation Display Area

- After execution the function block of initialization with no error, if the setting

condition of specified channel is normal then output ‘1’, or if abnormal, output 0’.

- No specified channel is ‘0’.-


REMARK

BOOL[8] and USINT[8] of data type means that the number of element is 8, and also this means the whole number of channels and channel

number.

4.2 Function Block for Local

REQ

BASE

SLOT

CH

TYPE

AVG_
EN
AVG_

NUM

AD3INI

STAT

ACT

DONE