Remark, 2) g6f-ad2a – LG G4F-AD3A User Manual

Page 31

Advertising
background image

Chapter 4. FUNCTION BLOCK

4 - 4

4.2.2 Module Reading-Array Type
1) G3F-AD3A, G4F-AD3A

Array type of function block for reading the module is performed for every channel in block and the specified
channels are used to read output variable of data displayed from A/D conversion digital value.

Function

block

I/O

Variable

Data

type

Descriptions

REQ

BOOL

Function Block Execution Request Area
- The execution of function block reading is requested in this area.

- If the status to be connected with this area is satisfied on the program operation

and input condition changes from low(0) to high(1), function block initialization for

the module is executed.

BASE

USINT

Base Location Number Area

- The base No. on which A/D conversion module is mounted is written on this area.

- Setting range : 0 to 3

SLOT

USINT

Slot Location Number Area

- The slot No. on which A/D conversion module is mounted is written on this area.

- Setting range: 0 to 7

Input

CH

BOOL[8]

Available Channel Specification Area

- Enabled channels are specified to 1 and disabled channels are specified to 0.

DONE

BOOL

Function Block Execution Complete Area

- When function block reading is executed with no error, 1 is written and until next

execution, 1 is continuing. When error occurs, 0 is written and operation come to

stop

STAT

USINT

Error Code Display Area

- When error occurs during function block reading, the error code number is written.

ACT

BOOL[8]

Channel Operation Display Area

- After execution the function block of initialization with no error, if the setting

condition of specified channel is normal then output ‘1’, or if abnormal, output 0’.

- No specified channel is ‘0’.-



output

DATA

INT[8]

A/D Conversion Value Output Area

Output data range : -48 ~ 4047

REMARK

BOOL[8] and USINT[8] of data type means that the number of element is 8, and also this means the whole number of channels and channel number.

2) G6F-AD2A

Array type of function block for reading is performed for all channels in module and the specified
channel is used to read output variable of data displayed from A/D conversion digital value.

Function

block

I/O

Variable

Data
type

Descriptions

REQ

BOOL

Function Block Execution Request Area

- The execution of function block reading is requested in this area.

- If input condition is changed from low(0) to high(1), function block initializatio n for

the module is executed.

BASE

USINT

Base Module Location Number Area

- The base No. on which A/D conversion module is mounted is written on this area.

- Setting range : 0

SLOT

USINT

Slot Location Number Area

- The slot No. on which A/D conversion module is mounted is written on this area.

- Setting range: 0 to 7

Input

CH

BOOL[4]

Available Channel Specification Area

- Available channels are specified in this area.

- Enabled channels are specified to 1 and disabled channels are specified to 0.

DONE

BOOL

Function Block Execution Complete Area
- When function block reading is executed with no error, 1 is written and 1 is kept

until next execution. When error occurs, 0 is written and operation come to stop

STAT

USINT

Error Code Display Area

- When error occurs during function block reading, the error code number is written.

- Error code is referred to Manual 4.3.

ACT

BOOL[4]

Channel Operation Display Area

- The channel specified after executing the function block read with no error is

right, 1 is written and, on the non-specified channel, 0 is written

Output

DATA

INT[4]

A/D Conversion Value Output Area

- Output data range : -48 ~ 4047 or –2048 ~ 2047

REQ

BASE

SLOT

CH

AD3ARD

STAT

ACT

DONE

DATA

REQ

BASE

SLOT

CH

DATA

AD2ARD

STAT

ACT

DONE

Advertising
This manual is related to the following products: