Ch8_mk programming.pdf, 8 mk programming, Chapter 8 mk programming – LG G4F-AD3A User Manual

Page 67: 1 basic programming, 1 g6f-ad2a

Advertising
background image

Chapter 8 MK Programming

8 - 1

8 MK Programming

8.1 Basic programming

The following example program shows how to set the operation condition for buffer memory of

A/D conversion module. In this example, assume that the A/D module is mounted on the slot 2.

8.1.1 G6F-AD2A

PUT 0002 00000 h000B 00001

PUT 0002 00001 00000 00001

PUT 0002 00002 h0009 00001

PUT 0002 00003 00100 00001

PUT 0002 00006 00050 00001

PUT 0002 00007 00001 00001

GET 0002 00008 D0108 00001

GET 0002 00009 D0109 00001

GET 0002 00011 D0111 00001

GET 0002 00012 D0112 00001

GET 0002 00013 D0113 00001

GET 0002 00014 D0114 00001

GET 0002 00016 D0116 00001

Slot

number

Buffer

memory

Data

No. of
words

Channel to be used
(use channel 0, 1, and 3)

Assign analog input
range (DC4 ~ 20mA)

Assign average
processing channel

(channel 0 and 3)

Set Averaging count of
channel 0 (100 times)

Set Averaging count of
channel 3 (50 times)

Validate the new setting
value

Execution

condition

Execution

condition

Slot

number

Buffer

memory

Destination

of data

No. of
words

Read the A/D converted
value of channel 0, and
store it into D0108

Read the A/D converted
value of channel 1, and
store it into D0109

Read the A/D converted
value of channel 3, and
store it into D0111

Read the operating
status, and store it into
D0112

Read the error code of
channel 0, and store it
into D0113

Read the error code of
channel 3, and store it
into D0114

Read the error code of
channel 4, and store it
into D0116

Advertising
This manual is related to the following products: