LG G4F-AD3A User Manual

Page 73

Advertising
background image

Chapter 8 MK Programming

8 - 7

8.2.3 An A/D module mounted on a remote station

1) System configuration

Fnet communication module on self-station : slot 2

Fnet remote module of remote station : station number 01

A/D module of remote station : slot 0, remote code = hC0

2) Initial setting of A/D module

No

Item

Setting

Buffer memory

address

Data to be

written

1

Channel to be used

Ch 0

0

h0001

2

Analog input type and range

0 ~ 10 VDC

1

h0001

3

Averaging processing enable

Ch 0

2

h0001

4

Averaging count

Ch 0 : 10 times

3

h000A

5

Validate setting

7

h0001

3) Description of program

When the digital converted value of channel 0 of remote A/D module is less than

2000, turns on P0010 of self-station.

When the digital converted value of channel 0 of remote A/D module is 2000 ~ 2999,

turns on P0011 of self-station.

When the digital converted value of channel 0 of remote A/D module is 3000 ~ 3999,

turns on P0012 of self-station.

When the digital converted value of channel 0 of remote A/D module is 4000 or

greater, turns on P0013 of self-station.

GM4-
PA2A

K4P-

15AS

G4X-

D22A

G4Q-

TR2A

G4L-

FUEA

P000

P001

P002

GM4-
PA2A

G4L-

RBEA

G4F-

AD3A

G4Q-

TR2A

Station

number : 01

Slot 0

P0000

Start switch for A/D

conversion