Chassis cooling – National Instruments PXI Express NI PXIe-1065 User Manual

Page 44

Advertising
background image

Appendix A

Specifications

© National Instruments Corporation

A-3

NI PXIe-1065 User Manual

Maximum ripple and noise (20 MHz bandwidth)

Over-current protection.......................... All outputs protected from short

circuit and overload with
automatic recovery

Over-voltage protection

3.3 V and 5 V .................................. Clamped at 20 to 30% above

nominal output voltage

Power supply shuttle MTTR .................. Replacement in under 5 minutes

Chassis Cooling

Module cooling system

NI PXIe-1065.................................. Forced air circulation

(positive pressurization) through
three 165 cfm fans with
High/Auto speed selector

Slot airflow direction ............................. Bottom of module to top of

module

Module cooling intake ........................... Bottom rear of chassis

Module cooling exhaust ......................... Along both sides and top of

chassis

Power supply cooling system................. Forced air circulation through

two integrated fans

Power supply cooling intake .................. Right side of chassis

Power supply cooling exhaust................ Left side of chassis

Voltage

Maximum Ripple and Noise

+3.3 V

50 mV

pp

+12 V

120 mV

pp

+5 V

50 mV

pp

–12 V

120 mV

pp

Advertising