Backplane – National Instruments PXI Express NI PXIe-1065 User Manual

Page 48

Advertising
background image

Appendix A

Specifications

© National Instruments Corporation

A-7

NI PXIe-1065 User Manual

Backplane

Size......................................................... 3U-sized; one system slot

(with three system expansion
slots) and 17 peripheral slots.
Compliant with IEEE 1101.10
mechanical packaging.
PXI Express Specification
compliant.
Accepts both PXI Express and
CompactPCI (PICMG 2.0 R 3.0)
3U modules.

Backplane bare-board material .............. UL 94 V-0 Recognized

Backplane connectors ............................ Conforms to IEC 917 and

IEC 1076-4-101, and are
UL 94 V-0 rated

System Synchronization Clocks (PXI_CLK10, PXIe_CLK100,
PXIe_SYNC100)

10 MHz System Reference Clock: PXI_CLK10

Maximum slot-to-slot skew ................... 1 ns

Accuracy ................................................ ±25 ppm max. (guaranteed over

the operating temperature range)

Maximum jitter ...................................... 5 ps RMS phase-jitter

(10 Hz–1 MHz range)

Duty-factor ............................................. 45%–55%

Unloaded signal swing ........................... 3.3 V ±0.3 V

Note

For other specifications refer to the PXI-1 Hardware Specification.

100 MHz System Reference Clock: PXIe_CLK100 and
PXIe_SYNC100

Maximum slot-to-slot skew ................... 100 ps

Accuracy ................................................ ±25 ppm max. (guaranteed over

the operating temperature range)

Advertising