Air ducting work, Caution, Installation reference – Toshiba RAV-SM561AT-E User Manual

Page 102: Connecting method of the duct

Advertising
background image

– 102 –

RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E

Installation reference

(Example for RAV-SM801BT model)

The air supply ducting work is classified in two ways, one is branched by the round ducts, and the other is branched
by the square ducts. (Be sure to divide the air supply duct into three or more branches.)

4

AIR DUCTING WORK

25mm or more

Ø150mm or more

Density of thermal
insulator (glass wool) is
24 kg/m³ or equivalent.

CAUTION

Incomplete thermal insulation of the supply air flange and sealing may cause dew drops.

In case of the square duct, apply the thermal insulator
of thickness 25mm or more to the duct board. For the
thermal insulator, use high-density glass wool of
weight 64kg/m

3

.

Thermal insulator with
sticking material
(50mm-width, 6mm (t))

Aluminum tape
(Seal : 50mm-width)

Aluminum tape
(Seal : 50mm-width)

Square duct board
25mm-thickness,
64kg/m³ or equivalent

Thermal insulator
with sticking material
(50mm-width, 6mm-thickness)

Screws
(6 pieces)

Screws
(6 pieces)

Flange
(procured locally)

Indoor unit side

Thermal insulator
at indoor unit side
Stuck already at
shipment from the factory

Fit to the arro

Fit to the arrow

w

direction by pushing.

Fit to the arrow
direction by pushing.

Fit to the arro

Fit to the arrow

w

direction by pushing.

Fit to the arrow
direction by pushing.

Seal/thermal insulator
with sticking material
(25mm-width, 6mm (t))

Seal/thermal insulator
with sticking material
(25mm-width, 6mm (t))

( )

( )

Thermal insulator
at indoor unit side
Stuck already at
shipment from the factory

( )

Attach by pushing to
the arrow direction.
(Outside corner direction)

( )

Thermal insulator
25mm-thickness,
24kg/m³ or equivalent

Round duct

Flange

Fit the seal/thermal insulator (25mm-width, 6mm-thickness)
by pushing to the arrow direction so that no gap can be
found between the flange and the round duct.

Fig. 2 (a)

Fig. 2 (b)

25mm or more

Duct board

Density of thermal
insulator (glass wool) is
64 kg/m³ or equivalent.

<Round duct>

In case of the round duct, use the thermal insulator of
thickness 25mm or more and inner diameter 150mm
or more to the duct board.
(If the inner diameter is not enough, resistance
increase, as the result, air does not flow smoothly and
loss of the static pressure increases.) For the thermal
insulator, use high-density glass wool of 24kg/m

3

or

equivalent.

<Square duct> (Reference for square duct)

When using the square duct, change the type of the air
supply flange from round type to square flange at the
local site.

Connecting method of the duct

1. Supply air side

<Round duct>

<Square duct>