– 5 –

RAV-SM561AT-E, RAV-SM801AT-E

• When the air conditioner is installed in a small room, provide appropriate measures to ensure

that the concentration of refrigerant leakage occur in the room does not exceed the critical
level.

• Install the air conditioner securely in a location where the base can sustain the weight adequately.

• Perform the specified installation work to guard against an earthquake.

If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.

• If refrigerant gas has leaked during the installation work, ventilate the room immediately.

If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.

• After the installation work, confirm that refrigerant gas does not leak.

If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas
might generate.

• Electrical work must be performed by a qualified electrician in accordance with the Installation

Manual. Make sure the air conditioner uses an exclusive power supply.
An insufficient power supply capacity or inappropriate installation may cause fire.

• Use the specified cables for wiring connect the terminals securely fix. To prevent external

forces applied to the terminals from affecting the terminals.

• Be sure to provide grounding.

Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables.

• Conform to the regulations of the local electric company when wiring the power supply.

Inappropriate grounding may cause electric shock.

• Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas.

If a combustible gas leaks, and stays around the unit, a fire may occur.

Required tools for installation work

1) Philips screwdriver
2) Hole core drill (65 mm)
3) Spanner
4) Pipe cutter
5) Knife
6) Reamer
7) Gas leak detector
8) Tape measure
9) Thermometer

10) Mega-tester

R410A (Special requirement)

17) Gauge manifold

(Charge hose : R410A special requirement)

18) Vacuum pump

(Charge hose : R410A special requirement)

19) Torque wrench

1/4 (17 mm) 16 N•m (1.6 kgf•m)
3/8 (22 mm) 42 N•m (4.2 kgf•m)
1/2 (26 mm) 55 N•m (5.5 kgf•m)
5/8 (15.9 mm) 120 N•m (12.0 kgf•m)

20) Copper pipe gauge adjusting projection margin
21) Vacuum pump adapter

11) Electro circuit tester
12) Hexagonal wrench
13) Flare tool
14) Pipe bender
15) Level vial
16) Metal saw

2

ACCESSORY AND REFRIGERANT

Accessory and Installation Parts

Refrigerant Piping

• Piping kit used for the conventional refrigerant cannot be

used.

• Use copper pipe with 0.8 mm or more thickness for Ш6.4,

Ш9.5, Ш12.7.

Use copper pipe with 1.0 mm or more thickness for Ø15.9.

• Flare nut and flare works are also different from those of the

conventional refrigerant. Take out the flare nut attached to the
main unit of the air conditioner, and use it.

Outdoor unit Installation manual × 1

1

2

Drain nipple

Waterproof rubber cap