Electrical work, Caution – Toshiba RAV-SM561AT-E User Manual

Page 13

Advertising
background image

– 13 –

RAV-SM561AT-E, RAV-SM801AT-E

Valve cover

Piping cover

Indoor/outdoor
connecting cables

Power cable

6

ELECTRICAL WORK

For the air conditioner that has no power cable,
connect a power cable as mentioned below.

How to wire

1. Connect the connecting cable to the terminal as

identified with their respective numbers on the
terminal block of indoor and outdoor unit.
H07 RN-F or 245 IEC 66 (1.0 mm

2

or more)

2. When connecting the connecting cable to the

outdoor unit terminal, prevent water coming in the
outdoor unit.

3. Insulate the unsheathed cords (conductors) with

electrical insulation tape. Process them so that they
do not touch any electrical or metal parts.

4. For inter connecting cable, do not use a wire

jointed to another on the way.

Use wires long enough to cover the entire length.

Power cable

Earth line Earth line

(mm)

10

10

10

10

L N

30

30

40

40

Connecting
cable

1 2 3

Tripping length power cord and connecting cable

CAUTION

• Wrong wiring may cause a burnout to some

electrical parts.

• Be sure to use the cord clamps attached to the

product.

• Do not damage or scratch the conductive core

and inner insulator of power and inter-connect-
ing cables when peeling them.

• Be sure to comply with local regulations of the

cable from outdoor unit to indoor unit.
(wire size and cabling method etc.)

• Use the power and Inter-connecting cables with

specified thickness, specified type and protec-
tive devices required.

How to remove the valve cover

1. Remove screws of the valve cover.

2. Pull the valve cover downward to remove it.

CAUTION

• The installation fuse (25A D type

) must

be used for the power supply line of this air
conditioner.

• Incorrect/incomplete wiring might cause an

electrical fire or smoke.

• Prepare the exclusive power supply for the air

conditioner.

• This product can be connected to the mains.

Connection to the fixed wiring :
A switch which disconnects all poles and has
a contact separation of at least 3 mm must be
incorporated in the fixed wiring.

Model

Power supply

Maximum running current

Installation fuse rating

Power cable

RAV-SM56, RAV-SM80

220 – 240 V

Single phase 50 Hz

15 A

25 A (D type

)

H07 RN-F or 245 IEC 66

(2.5 mm

2

or more)

Terminal block

1

2

3

L

N

Screw

Connecting

cable

Power cable