DRAIN PIPING WORK

REQUIREMENT

• Be sure to perform heat insulation of the drain pipes of the indoor unit.

• Never forget to perform heat insulation of the connecting part with the indoor

unit. An incomplete heat insulation causes dewing.

• Set the drain pipe with downward slope (1/100 or more), and do not make

swelling or trap on the piping. It may cause an abnormal sound.

• For length of the traversing drain pipe, restrict to 20m or less.

In case of a long pipe, provide support brackets with interval of
1.5 to 2m in order to prevent waving.

CAUTION

• Following the Installation Manual,

perform the drain piping work so that
water is properly drained, and apply a
heat insulation so as not to cause a dew.
Inappropriate piping work may result in
water leakage in the room and wet of
furniture.

Piping/Heat insulating material

Require the following materials for piping and heat
insulating at site.

Trap

Arched
shape

Support
bracket

1/100 or more
downward

Heat
insulator

1.5m to 2m

As long as possible (10cm)

VP30 or more

Downward slope
1/100 or more

VP25

VP25

VP25

Extended
ventilating pipe

Adhesive inhibited :

Use the attached flexible hose and hose band for connecting the drain hose to the clear drain socket.

If applying the adhesive, socket will be damaged and cause water leakage.

Drain up

When not securing down slope on the drain pipe, use a drain up kit sold separately.

Also refer to the “Drain up kit installation manual”.

The drain pipe can be raised 60cm from the top face of the main unit.

* When using drain up kit, both drain pipe and refrigerant pipe can be taken only from upper side.

Piping

Heat insulator

Hard vinyl chloride pipe VP20
(Outer dia. : Ø26mm)

Foam polyethylene :
Thickness 10mm or more

<Collective piping>

• Set the collective piping as shown

in the right figure.

• Be sure not to apply force to the connecting part

of the drain pipe.

• The hard vinyl-chloride pipe cannot be directly

connected to the drain pipe connecting port of
the indoor unit.

For connection with the drain pipe connecting
port, be sure to use/fix the attached flexible hose
with the hose band, otherwise a damage or
water leak is caused on the drain pipe
connecting port.

Attached hose band

Soft socket

Soft socket

Attached hose band

Attached flexible hose

Drain pipe connecting port

(Hard socket)

VP20 vinyl chloride pipe

(procured locally)

Adhesive agent

prohibited

Drain pan