– 9 –

RAV-SM561AT-E, RAV-SM801AT-E

Optional Installation Parts (Local Procure)

Refrigerant Piping Connection

<Piping connection>

A

B

C

Parts name

Refrigerant piping
Liquid side : Ø6.4 mm or Ø9.5 mm
Gas side : Ø12.7 mm or Ø15.9 mm

Pipe insulating material (polyethylene
foam, 6 mm thick)

Putty, PVC tapes

Q’ty

Each one

1

Each one

CAUTION

TAKE NOTICE THESE IMPORTANT 4 POINTS BELOW FOR PIPING WORK

1. Keep dust and moisture away from inside the connecting pipes.

2. Tightly connect the connection between pipes and the unit.

3. Evacuate the air in the connecting pipes using VACUUM PUMP.

4. Check gas leak at connected points.

Capacity

rank

RAV-

SM56

SM80

Liquid side

Outer

Thickness

diameter

Ш6.4

0.8

Ш9.5

0.8

Gas side

Outer

Thickness

diameter

Ш12.7

0.8

Ш15.9

1.0

4

REFRIGERANT PIPING

90˚

Obliquity

OK

NO GOOD

Roughness

Warp

Flaring

1. Cut the pipe with a pipe cutter.

2. Insert a flare nut into the pipe, and flare the pipe.

As the flaring sizes of R410A differ from those of
refrigerant R22, the flare tools newly manufactured
for R410A are recommended.
However, the conventional tools can be used by
adjusting projection margin of the copper pipe.

• Flaring size : A (Unit : mm)

A

* In case of flaring for R410A with the conventional

flare tool, pull it out approx. 0.5 mm more than that
of R22 to adjust to the specified flare size.
The copper pipe gauge is useful for adjusting
projection margin size.

• Projection margin in flaring :

B (Unit : mm)

Rigid (Clutch type)

Imperial (Wing nut type)

Outer diam.

of copper

pipe

6.4

9.5

12.7

15.9

R410A tool used

R410A

R22

0 to 0.5

(Same as left)

0 to 0.5

(Same as left)

0 to 0.5

(Same as left)

0 to 0.5

(Same as left)

Conventional tool used

R410A

R22

1.0 to 1.5

0.5 to 1.0

1.0 to 1.5

0.5 to 1.0

1.0 to 1.5

0.5 to 1.0

1.0 to 1.5

0.5 to 1.0

Outer diam. of copper pipe

6.4

9.5

12.7

15.9

R410A

R22

1.5 to 2.0

1.0 to 1.5

1.5 to 2.0

1.0 to 1.5

2.0 to 2.5

1.5 to 2.0

2.0 to 2.5

1.5 to 2.0

+0
- 0.4

A

R410A

R22

9.1

9.0

13.2

13.0

16.6

16.2

19.7

19.4

Outer diam. of copper pipe

6.4

9.5

12.7

15.9

B