Change of lighting time of filter sign

According to the installation condition, the lighting time
of the filter sign (Notification of filter cleaning) can be
changed.

Follow to the basic operation procedure

(

1

2

3

4

5

6

).

• For the item code in Procedure

3

, specify [01].

• For the set data in Procedure

4

, select the setup

data of lighting time of filter sign to be changed from
the table below.

To secure better effect of heating

When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator, etc. to circulate heat air
near the ceiling.

Follow to the basic operation procedure

(

1

2

3

4

5

6

).

• For the item code in Procedure

3

, specify [06].

• For the set data in Procedure

4

, select the setup

data of shift value of detection temperature to be set
up from the table below.

Set data

0000

0001

0002

0003

0004

Filter sign lighting time

None

150H

2500H (At shipment)

5000H

10000H

Set data

0000

0001

0002

0003

0004

0005

0006

Shift value of detection temp.

No shift

+1°C

+2°C (At shipment)

+3°C

+4°C

+5°C

+6°C

Check and test operation

Be sure to test the pipe connections for gas leak.

• Check the flare nut connections, valve stem cap

connections and service port cap connections for
gas leak with a leak detector or some soap water.